Voltage Drop
Definition
Voltage drop is the volts lost to resistance in the cable. For copper DC at 75 °C (NEC Chapter 9 Table 8), VD = (2 × 12.9 × I × L) / CM, where L is one-way feet and the 2 covers the round-trip conductor. Percent drop = VD ÷ system volts. A 3% budget is a performance target so inverters and LED drivers do not brown out. Ampacity (how hot the insulation gets) is a separate limit — a cable can meet 3% drop and still be too thin to carry the current safely.
Calculators that use this
Wiring and electrical safety
DC Voltage Drop Calculator
Calculate copper DC voltage drop in volts and percent for a chosen AWG, current and one-way cable length.
Wiring and electrical safety
12V/24V/48V DC Wire Gauge (AWG) Calculator
Pick a copper AWG size for 12V, 24V or 48V DC runs from current, one-way length and a 3% voltage-drop budget.