Off-Grid Solar Calculators
12V/24V/48V DC Wire Gauge (AWG) Calculator
https://www.offgridsizing.com/calculators/dc-wire-gauge/
Engineering estimate only — not a system design. Verify with a licensed electrician.
12V/24V/48V DC Wire Gauge (AWG) Calculator
Pick copper AWG for 12V, 24V or 48V DC from current, one-way length and a 3% drop budget. Voltage drop is VD = (2 × 12.9 × I × L) / CM (NEC Chapter 9 Table 8, copper 75 °C). Enter the one-way length; the formula already doubles the run. The size must also meet the copper ampacity limit (NEC Table 310.16, 90 °C column).
Off-grid system flow
Follow the DC path. Nodes open the matching sizer; arrows open the wire-gauge tool for that run.
Inputs
Results
Please tick the box above to display the Result.
Engineering methodology
Imperial copper voltage drop VD = (2 × K × I × L) / CM, with K = 12.9 at 75 °C from NEC Chapter 9 Table 8. L is one-way feet; the 2 covers the round-trip conductor. Required circular mils = (2 × 12.9 × I × L) ÷ allowed volts, where allowed volts = system volts × (max % ÷ 100). Metric equivalent: resistivity ρ = 0.02145 Ω·mm²/m (same 75 °C copper as K = 12.9), so VD = (2 × ρ × I × L) / mm² and required mm² = (2 × ρ × I × L) ÷ allowed volts, with L in one-way metres. The chosen IEC 60228 size (or AWG) must also meet an ampacity limit — the NEC Table 310.16 copper 90 °C column for AWG, or IEC 60364-5-52 Table B.52.4 method C (70 °C PVC, 30 °C ambient) for mm². On 14, 12 and 10 AWG, NEC 240.4(D) also caps the current at 15, 20 and 30 A, because no larger fuse may protect them. Terminals listed at 75 °C can cap the circuit below the 90 °C column under NEC 110.14(C). 3% drop is a common DC performance target, not an ampacity limit. This tool is copper only; it does not apply aluminium, grouping or soil correction.
Related calculations
- voltage drop on a chosen AWG — same VD = (2 × 12.9 × I × L) / CM formula
- fuse that protects that cable — 1.25 × continuous current, not above ampacity
- load watts that set the current — I = P ÷ V before you pick AWG
Why 12V DC needs thicker cable than 48V
For the same load watts, current quadruples when you go from 48 V to 12 V (I = P ÷ V): 1,200 W is 25 A at 48 V but 100 A at 12 V. Voltage drop is I × R (Ohm’s law), and a 3% budget at 12 V is only 0.36 V. NEC Chapter 9 Table 8 copper at 75 °C uses K = 12.9 in VD = (2 × K × I × L) / CM, with L one-way feet.
3% drop is not ampacity
Percent voltage drop is a performance target so inverters and LED drivers do not brown out. Ampacity is how much current the insulation can take without overheating. This tool enforces both a drop budget and the NEC Table 310.16 copper 90 °C ampacity column, which NEC 240.4(D) caps at 15, 20 and 30 A on 14, 12 and 10 AWG. Because most listed terminals are rated only 75 °C, NEC 110.14(C) can force a thicker size than the table used here — so can bundling or 60 °C insulation.
Frequently asked questions
Is the cable length one-way or round-trip for voltage drop?
Enter one-way feet. The formula already multiplies by 2 for the outgoing and return conductors. Using round-trip length would double the drop again and oversize the cable.
Why do 12 V systems need much thicker wire than 48 V?
For the same watts, current I = P ÷ V. Drop VD = I × R (Ohm’s law). Lower voltage means higher current and a larger fraction of system voltage for the same ohms. A 3% budget at 12 V is only 0.36 V.
Is 3% voltage drop a fire-safety ampacity limit?
No. Percent drop is a performance budget. Ampacity (heat in the insulation) is a separate table. This tool refuses a size below the ampacity in its table, but 75 °C terminals, bundling, engine rooms and 60 °C insulation can need a thicker cable than that table.
More in this cluster
All tools in this clusterWiring and electrical safety
DC Inline Fuse & Circuit Breaker Sizer
Size a DC fuse or breaker at 125% of continuous current, then check it against copper cable ampacity.
Wiring and electrical safety
DC Voltage Drop Calculator
Calculate copper DC voltage drop in volts and percent for a chosen AWG, current and one-way cable length.
Wiring and electrical safety
Grounding Rod & Wire Sizer
Estimate copper GEC size for a ground rod or other electrode and EGC size from the DC overcurrent device.
Wiring and electrical safety
Solar Combiner Box Fuse Sizer
Size PV string and combiner fuses at 1.56 × Isc and see when three or more parallel strings need fusing.