Solar Combiner Box Fuse Sizer
Size PV string and combiner fuses at 1.56 × Isc (NEC 690.8 combined with 690.9). Three or more equal parallel strings typically need a fuse on every string, never above the module maximum series-fuse label. Two strings can often skip fuses when the conductors are already sized for 1.56 × Isc.
Off-grid system flow
Follow the DC path. Nodes open the matching sizer; arrows open the wire-gauge tool for that run.
Inputs
Results
Please tick the box above to display the Result.
Engineering methodology
NEC 690.8 and 690.9 stack two 125% factors: maximum circuit current is 1.25 × Isc, and the overcurrent device is at least 1.25 × that, which is 1.5625 × Isc, usually written as 1.56 × Isc. String fuse = next standard size ≥ 1.56 × Isc, never above the module maximum series-fuse label (the result is invalid if it would exceed that label). Combiner output fuse ≥ 1.56 × Isc × number of strings. String fuses are flagged as typically required at three or more equal parallel strings. This tool does not size cable length or voltage drop.
Related calculations
- how many strings and what Isc you paralleled — fusing usually starts at three equal strings
- battery-side DC fuse math — 1.25 × load is not the same as 1.56 × Isc
- controller current after the combiner — output fuse and MPPT amps are related but not identical
Why PV fuses are 1.56 × Isc
NEC 690.8 takes maximum circuit current as 1.25 × Isc. 690.9 then sizes the overcurrent device at least 125% of that continuous current. 1.25 × 1.25 = 1.5625 ≈ 1.56 × Isc. The next standard fuse must not exceed the module maximum series-fuse label.
Two strings vs three or more
Two equal strings often skip string fuses if each conductor is already sized for 1.56 × Isc: backfeed is about 1.25 × Isc. Three strings can push about 2.5 × Isc into a fault, which exceeds typical module withstand, so string fuses are the usual case.
Frequently asked questions
Why 1.56 times Isc for PV fuses?
1.25 × Isc is the maximum circuit current under 690.8. Overcurrent devices for continuous PV current are then at least 125% of that value under 690.9, so 1.25 × 1.25 = 1.5625, usually rounded to 1.56 × Isc. The tool uses the exact 1.5625.
Do two parallel solar strings need fuses?
Often no, if each conductor is already sized to 1.56 × Isc: a faulted string sees about 1.25 × Isc from the other string, which modules and that wiring can usually withstand. Three or more strings can backfeed ~2.5 × Isc, so string fuses are the usual case.
Can I exceed the module “maximum series fuse” rating?
No. That label is a reverse-current withstand limit (UL 61730 / nameplate). The string fuse must be at least 1.56 × Isc and not larger than that maximum. This tool marks the result invalid if the next standard fuse is above the label.
More in this cluster
All tools in this clusterWiring and electrical safety
DC Inline Fuse & Circuit Breaker Sizer
Size a DC fuse or breaker at 125% of continuous current, then check it against copper cable ampacity.
Wiring and electrical safety
DC Voltage Drop Calculator
Calculate copper DC voltage drop in volts and percent for a chosen AWG, current and one-way cable length.
Wiring and electrical safety
12V/24V/48V DC Wire Gauge (AWG) Calculator
Pick a copper AWG size for 12V, 24V or 48V DC runs from current, one-way length and a 3% voltage-drop budget.
Wiring and electrical safety
Grounding Rod & Wire Sizer
Estimate copper GEC size for a ground rod or other electrode and EGC size from the DC overcurrent device.