DC Inline Fuse & Circuit Breaker Sizer
https://www.offgridsizing.com/calculators/dc-fuse-sizer/
Engineering estimate only — not a system design. Verify with a licensed electrician.
DC Inline Fuse & Circuit Breaker Sizer
Protect the wire, not the gadget. A 40 A continuous load on 6 AWG needs a fuse of at least 1.25 × 40 A = 50 A, rounded up to the next standard size, and that fuse must not exceed the cable’s ampacity (75 A). On 14, 12 and 10 AWG, NEC 240.4(D) also caps the fuse at 15, 20 and 30 A. If the fuse does not fit, use thicker cable.
Off-grid system flow
Follow the DC path. Nodes open the matching sizer; arrows open the wire-gauge tool for that run.
Inputs
Results
Please tick the box above to display the Result.
Engineering methodology
Protect the conductor, not the gadget. Minimum overcurrent device = 1.25 × continuous current (NEC-style continuous-load factor). The tool picks the next standard fuse size (NEC 240.6(A)) and compares it with the NEC Table 310.16 copper 90 °C ampacity for the chosen AWG, or with IEC 60364-5-52 Table B.52.4 method C (70 °C PVC) when mm² is shown. On 14, 12 and 10 AWG copper, NEC 240.4(D) caps the fuse at 15, 20 and 30 A, below their table ampacity. Terminals listed at 75 °C can cap the circuit lower under NEC 110.14(C). If that fuse would exceed the cable’s limit, the result is invalid: upsize the cable. A 3% voltage-drop target is not an ampacity limit.
Related calculations
- thicker cable if the fuse will not fit — never upsize the fuse past ampacity
- PV string fuses at 1.56 × Isc — solar OCPD uses a different NEC 690 factor
- EGC from the same OCPD rating — Table 250.122 follows the fuse or breaker size
Frequently asked questions
Why size a DC fuse at 125% of load current?
Continuous loads (3 hours or more) are fused at not less than 125% of the current so the fuse or breaker does not nuisance-trip as it heats. The fuse still must not exceed the wire’s ampacity, because the wire is the protected object.
Should the fuse match the appliance rating or the cable?
The cable. An undersized fuse on a fat cable is a nuisance; an oversized fuse on a thin cable is a fire risk. Place the fuse as close to the battery positive as practical.
What if no standard fuse fits between 1.25 × amps and the cable’s limit?
This calculator marks that invalid. Use thicker cable so its limit reaches the next standard fuse, or reduce the continuous current. Do not install a fuse larger than the wire can carry.
More in this cluster
All tools in this clusterWiring and electrical safety
DC Voltage Drop Calculator
Calculate copper DC voltage drop in volts and percent for a chosen AWG, current and one-way cable length.
Wiring and electrical safety
12V/24V/48V DC Wire Gauge (AWG) Calculator
Pick a copper AWG size for 12V, 24V or 48V DC runs from current, one-way length and a 3% voltage-drop budget.
Wiring and electrical safety
Grounding Rod & Wire Sizer
Estimate copper GEC size for a ground rod or other electrode and EGC size from the DC overcurrent device.
Wiring and electrical safety
Solar Combiner Box Fuse Sizer
Size PV string and combiner fuses at 1.56 × Isc and see when three or more parallel strings need fusing.