Grounding Rod & Wire Sizer
Two different conductors. The grounding electrode conductor (GEC) runs to the rod or other electrode. The equipment grounding conductor (EGC) follows the circuit so metal cases have a fault path.
Off-grid system flow
Follow the DC path. Nodes open the matching sizer; arrows open the wire-gauge tool for that run.
Inputs
Results
Please tick the box above to display the Result.
Engineering methodology
Two different conductors. The grounding electrode conductor (GEC) runs to the electrode. Under NEC 250.166 it is not smaller than the largest supplied conductor, not smaller than 8 AWG copper, and need not be larger than 3/0. The “rod, pipe or plate (sole connection)” choice adds the 250.166(C) cap: the GEC need not be larger than 6 AWG copper, so it is 8 AWG with small circuit conductors and 6 AWG once the largest conductor reaches 6 AWG. The narrower exemptions for a concrete-encased electrode (250.166(D) caps it at 4 AWG) and a ground ring (250.166(E) caps it at the ring conductor) are not implemented, so those electrodes may be oversized here. The equipment grounding conductor (EGC) follows a simplified NEC Table 250.122 by overcurrent-device rating. Metric mm² inputs are mapped up to the first AWG at least as large (25 mm² counts as 2 AWG), because the GEC must not be smaller than the conductor; displayed mm² are AWG equivalents, not an IEC 60364-5-54 earthing table.
Related calculations
- OCPD rating that sizes the EGC — Table 250.122 follows the fuse or breaker
- largest ungrounded conductor AWG — the GEC follows that size up to the electrode cap
Frequently asked questions
What is the difference between a GEC and an EGC?
The GEC connects the system to the grounding electrode (rod, pipe, plate, ring). The EGC runs with the circuit, so a fault to a metal case has a path back to the source and the OCPD opens. This tool sizes both; it does not design the whole grounding-electrode system.
Why is a ground-rod GEC capped at 6 AWG copper?
NEC 250.166(C): where it is the sole connection to a rod, pipe or plate electrode, the GEC need not be larger than 6 AWG copper. A 4/0 battery cable does not force a 4/0 GEC to a single rod. It is a cap, not a fixed size: with circuit conductors of 8 AWG or smaller the general 8 AWG minimum applies.
Does Table 250.122 apply to DC off-grid systems?
EGC sizing by OCPD rating is the usual NEC approach this tool copies in simplified breakpoints. DC bonding of negative, chassis and AC equipment grounds is a separate design choice for a qualified electrician.
More in this cluster
All tools in this clusterWiring and electrical safety
DC Inline Fuse & Circuit Breaker Sizer
Size a DC fuse or breaker at 125% of continuous current, then check it against copper cable ampacity.
Wiring and electrical safety
DC Voltage Drop Calculator
Calculate copper DC voltage drop in volts and percent for a chosen AWG, current and one-way cable length.
Wiring and electrical safety
12V/24V/48V DC Wire Gauge (AWG) Calculator
Pick a copper AWG size for 12V, 24V or 48V DC runs from current, one-way length and a 3% voltage-drop budget.
Wiring and electrical safety
Solar Combiner Box Fuse Sizer
Size PV string and combiner fuses at 1.56 × Isc and see when three or more parallel strings need fusing.